Choosing Circuit Breakers for DC: MCB vs MCCB vs ACB

Einführung

Selecting the right circuit breaker for DC applications requires understanding the fundamental differences between Miniature Circuit Breakers (MCB), Molded Case Circuit Breakers (MCCB), and Air Circuit Breakers (ACB). Each technology serves distinct current ranges, offers different features, and carries significantly different costs—choosing incorrectly results in either inadequate protection or unnecessary expense.

This comprehensive comparison examines MCB vs MCCB vs ACB technologies from the decision-maker’s perspective. We analyze current ranges, physical characteristics, adjustability features, breaking capacities, installation requirements, and total cost of ownership. Beyond technical specifications, we provide decision matrices and application-specific recommendations for solar PV, battery storage, and industrial DC systems.

For electrical designers, project managers, and procurement specialists evaluating DC protection equipment, this guide delivers the comparative analysis needed to specify the optimal breaker technology for each application.

💡 Selection Priority: Choose breaker type based on current range first (MCB: <125A, MCCB: 15-2500A, ACB: >630A), then evaluate features (adjustability, metering) and budget. Technology overlap zones (50-125A, 630-1000A) require detailed cost-benefit analysis.

Fundamental Technology Differences

Physical Construction Comparison

MerkmalMCB (Miniature)MCCB (Molded Case)ACB (Air Circuit)
Housing MaterialThermoplastic
Polyamide, PC
Molded epoxy
Glass-filled
Metal chassis
Stahl, Aluminium
Typical Width9-72mm
(1-4 modules)
45-140mm
Fixed size
200-600mm
Drawer or fixed
Weight0.1-0.5 kg0.5-5 kg10-150 kg
MontageDIN rail snap-on
35mm rail
Panel mount
Bolt-on
Floor/wall mount
Drawer chassis
Installation Time2-5 minutes
Tool-free
15-30 minutes
Bolting required
2-8 hours
Rigging, alignment
Field ServiceabilityNon-serviceable
Replace entire unit
Limited
Some models repairable
Fully serviceable
Replace components

Current Rating Ranges

MCB (Miniature Circuit Breaker):
Range: 0.5A to 125A
Common ratings: 6A, 10A, 16A, 20A, 25A, 32A, 40A, 50A, 63A, 80A, 100A, 125A
Typische Anwendungen: Individual circuits, string protection, sub-distribution
Standard: IEC 60947-2, UL 489

MCCB (Molded Case Circuit Breaker):
Range: 15A to 2500A
Common ratings: 50A, 63A, 100A, 125A, 160A, 200A, 250A, 400A, 630A, 800A, 1000A, 1600A
Typische Anwendungen: Main distribution, large loads, industrial equipment
Standard: IEC 60947-2, UL 489

ACB (Air Circuit Breaker):
Range: 630A to 6300A
Common ratings: 800A, 1000A, 1250A, 1600A, 2000A, 2500A, 3200A, 4000A, 5000A, 6300A
Typische Anwendungen: Main switchgear, utility interconnection, large facilities
Standard: IEC 60947-2, UL 1066

Overlap Zones:
50-125A: MCB and MCCB both available—decision based on features/cost
630-1000A: MCCB and ACB both available—decision based on adjustability needs

Trip Mechanism Technologies

MCB – Fixed Thermal-Magnetic:
– Bimetallic thermal element (non-adjustable)
– Electromagnetic magnetic element (non-adjustable)
– Trip curves: B, C, D, Z (factory-set, cannot change)
– Response time: Fixed per curve type

MCCB – Semi-Adjustable or Electronic:
Standard MCCB: Fixed thermal, adjustable magnetic (50-100% range)
Electronic MCCB: Fully programmable via microprocessor
– Adjustable thermal trip: 0.4-1.0× In
– Adjustable magnetic trip: 1.5-10× In
– Adjustable time delays: 0.1-30 seconds
– Ground fault protection option

ACB – Fully Electronic Protection:
– Advanced microprocessor control
– Multiple protection functions:
– Long-time (I), Short-time (I²t), Instantaneous (I), Ground fault (Ig)
– LCD display showing current, energy, power factor
– Communication interfaces (Modbus, Profibus, Ethernet)
– Event logging and fault recording

Circuit breaker for DC technology selection matrix comparing MCB MCCB and ACB based on current ranges feature requirements cost considerations and typical applications with advantages and limitations

Feature-by-Feature Comparison

Adjustability and Coordination

MCB – No Adjustability:
– ✅ Advantage: Consistent, predictable performance
– ✅ Advantage: No field misconfiguration risk
– ❌ Limitation: Cannot optimize for specific loads
– ❌ Limitation: Difficult coordination with upstream devices

Szenario: 32A MCB, C-curve
– Thermal trip: Fixed at 1.45× In (46.4A)
– Magnetic trip: Fixed at 5-10× In (160-320A)
Cannot adjust either parameter

MCCB – Partial Adjustability:
– ✅ Thermal adjustment: ±20% on most models (0.8-1.0× In)
– ✅ Magnetic adjustment: 50-100% range (5-10× In typical)
– ✅ Enables coordination: Adjust magnetic trip for selectivity
– ❌ No time delay: Instantaneous magnetic trip

Szenario: 250A MCCB, adjustable
– Thermal: 200-250A range
– Magnetic: 1250-2500A range
– Can tune for load and upstream coordination

ACB – Full Programmability:
– ✅ Multi-function protection: Long-time, short-time, instantaneous, ground fault
– ✅ Time-current curves: Programmable I²t characteristics
– ✅ Zone selectivity: Communication-based coordination
– ✅ Load profiling: Adjust for specific load behavior

Szenario: 2000A ACB, electronic
– Long-time (thermal): 0.4-1.0× In, 2-300s delay
– Short-time (I²t): 1.5-10× In, 0.1-0.5s delay
– Instantaneous: 2-15× In, <50ms – Ground fault: 0.2-1.0× In, 0.1-1.0s delay – Each function independently programmable

Breaking Capacity (Icn)

MCB Typical Breaking Capacities:
Standard duty: 3-6 kA (residential solar)
Enhanced duty: 10 kA (commercial solar)
High breaking: 15-25 kA (industrial, utility-scale)

Physical Limitation: Contact gap and arc chute size constrain maximum breaking capacity. Achieving >25 kA in MCB form factor becomes impractical.

MCCB Breaking Capacities:
Standard: 25-35 kA (most applications)
High breaking: 50-65 kA (near transformer locations)
Very high: 85-150 kA (utility interconnection)

Advanced arc chutes and larger contact gaps enable higher breaking capacities.

ACB Breaking Capacities:
Standard: 50-65 kA
Hoch: 80-100 kA
Ultra-high: 120-150 kA (special designs)

Sophisticated arc extinction systems with magnetic blow-out and multiple chutes achieve extreme breaking capacities.

Auswirkungen auf die Kosten:
– Breaking capacity is expensive feature
– 10 kA MCB: $30-50
– 25 kA MCB: $80-120 (2-3× cost for 2.5× breaking capacity)
– 50 kA MCCB: $300-500
– 100 kA MCCB: $800-1200

Selection Rule: Specify breaking capacity based on maximum available fault current at installation point. Don’t overspecify—wastes budget.

Metering and Communication Capabilities

MCB – No Metering:
– No current measurement
– No voltage measurement
– No communication interface
– Purely protective device

MCCB Options:

Standard MCCB:
– No metering (like MCB)

MCCB with Electronic Trip Unit:
– Current measurement: ±2% accuracy
– Basic display: 4-digit LCD showing I
– Optional: kWh energy metering
– Optional: Modbus RTU communication
Cost premium: +30-50% over standard MCCB

ACB – Comprehensive Metering:
Electrical parameters:
– Current: 3-phase + neutral, 0.5% accuracy
– Voltage: 3-phase + neutral
– Power: kW, kVAR, kVA, power factor
– Energy: kWh, kVARh
– Harmonics: THD analysis
Display: Color LCD touchscreen
Communication:
– Modbus TCP/RTU
– Profibus DP
– Ethernet/IP
– IEC 61850 (utility applications)
Data logging: Fault records, event logs, waveform capture

Value Proposition:
– ACB metering eliminates need for separate power meter
– Typical power meter: $500-1500
– ACB with metering: +$1000-2000 over basic ACB
– Net cost: Comparable, but integrated solution

Installation and Maintenance Requirements

MCB Installation:
Labor: 2-5 minutes per breaker
Tools: None (snap-on DIN rail)
Torque: Standard screwdriver (2.0-3.5 Nm)
Skills: Basic electrician
Inbetriebnahme: Visual check, continuity test

MCCB Installation:
Labor: 15-30 minutes per breaker
Tools: Torque wrench, drill, bolts
Torque: 10-20 Nm (terminals)
Skills: Journeyman electrician
Inbetriebnahme: Visual, continuity, insulation resistance, trip test

ACB Installation:
Labor: 2-8 hours (including rigging)
Tools: Crane/hoist, alignment tools, torque wrenches
Torque: 50-200 Nm (bus connections)
Skills: Specialized technician
Inbetriebnahme: Full relay testing, primary injection test, secondary injection test, communication verification, metering calibration

Maintenance Comparison:

AspektMCBMCCBACB
Scheduled maintenanceNoneAnnual visualQuarterly inspection
Trip testingNot performed3-5 yearsJährlich
Contact inspectionReplace unit5-10 yearsJährlich
CalibrationN/AN/A (fixed)2-5 Jahre
Typical lifespan15-20 years20-30 years30-40 years
Repair possibilityNo, replaceLimitedYes, full

Lifecycle Cost Impact:
– MCB: Low maintenance, but full replacement on failure
– MCCB: Moderate maintenance, some repairs possible
– ACB: High maintenance cost, but extended life and component replacement lowers total cost

Physical size comparison of MCB MCCB and ACB circuit breakers for DC applications showing relative dimensions mounting methods and installation requirements

Application-Specific Selection Guide

Solar PV Systems

Residential Systems (3-10 kW):

String Protection (I_sc = 8-12A):
Technology: MCB
Bewertung: 16-20A
Type: C-curve, 2-pole
Voltage: 1000V or 1500V DC
Breaking: 6-10 kA
Quantity: 1-4 per system
Cost per breaker: $30-60
Rationale: Fixed protection adequate, high density needed in combiner box

Array Main (total I_sc = 40-60A):
Technology: MCB or entry-level MCCB
Bewertung: 63-80A
MCB option: $80-120
MCCB option: $200-300
Decision factor: If adjustability needed for future expansion → MCCB; otherwise MCB

Commercial Systems (50-500 kW):

String Protection (I_sc = 10-15A):
Technology: MCB
– Same rationale as residential
Quantity: 10-50+ per system

Array Main (total I_sc = 300-800A):
Technology: MCCB (required for current range)
Bewertung: 400-1000A
Type: Electronic trip unit preferred
Features needed:
– Adjustable magnetic trip for coordination
– Ground fault protection (optional but recommended)
– Communication for SCADA integration
Kosten: $800-2500
Rationale: High currents require MCCB technology; electronic features enable system monitoring

Utility-Scale Systems (1-100 MW):

String/Combiner Protection (I_sc = 200-500A):
Technology: MCCB
Bewertung: 250-630A
Electronic trip: Required for coordination

Main Array Disconnect (I_sc = 2000-10,000A):
Technology: ACB
Bewertung: 2500-12,000A
Features required:
– Full electronic protection with ground fault
– Metering integration (eliminates separate meter)
– Communication to central SCADA
– Event logging for troubleshooting
– Drawout design for maintenance
Kosten: $15,000-50,000
Rationale: Extreme currents, utility interconnection requirements, and monitoring needs mandate ACB technology

Battery Energy Storage Systems

Residential ESS (5-20 kWh, 48V):

Battery Main Disconnect (continuous 100-200A, surge 300-600A):
Technology: MCCB (required for current range)
Bewertung: 125-250A
Type: C or D-curve depending on surge profile
Breaking: 10-15 kA (battery fault currents very high)
Kosten: $200-400
Rationale: MCB insufficient for current; MCCB provides needed breaking capacity

Commercial ESS (100-500 kWh, 400-800V):

Battery String Protection (continuous 200-400A):
Technology: MCCB
Bewertung: 250-500A
Electronic trip: Recommended
Features needed:
– Ground fault protection (critical for safety)
– Communication for BMS integration
Kosten: $500-1200

Utility ESS Main (2000-5000A):
Technology: ACB
Full metering: Required
Communication: IEC 61850 to grid operator
Kosten: $20,000-60,000

Industrial DC Distribution

48V DC Data Center Distribution:

Server Rack Feeders (20-40A):
Technology: MCB
Voltage: 60-80V DC
Cost-effective: High-density panel distribution

Main DC Bus (2000-4000A):
Technology: ACB
Metering: Essential for PUE monitoring
Communication: Integration to DCIM (Data Center Infrastructure Management)

Total cost of ownership analysis for MCB MCCB and ACB circuit breakers comparing initial capital installation labor maintenance costs replacement expenses and downtime impact over 10-year lifecycle

Decision Matrix for Procurement

Selection Criteria Weighting

For Cost-Sensitive Projects (Residential, small commercial):
– Current range: 60%
– Initial cost: 30%
– Features: 10%
Ergebnis: MCB dominates for <63A applications For Performance-Critical Projects (Industrial, utility):
– Current range: 40%
– Features (adjustability, metering): 40%
– Reliability: 20%
Ergebnis: MCCB/ACB preferred even when MCB technically sufficient

For Grid-Interactive Projects (Solar farms, ESS):
– Communication requirements: 40%
– Metering needs: 30%
– Current range: 30%
Ergebnis: Electronic MCCB or ACB mandatory for utility compliance

When to Choose Each Technology

Choose MCB When:
✅ Current ≤ 63A (ideal) or ≤ 125A (acceptable)
✅ Fixed protection acceptable (no adjustment needed)
✅ Budget constrained
✅ High-density installation (limited panel space)
✅ Fast installation required
✅ Residential or light commercial application
✅ No communication/metering requirements

Beispiel: Solar PV string protection, small loads, distribution sub-panels

Choose MCCB When:
✅ Current 50-2500A range
✅ Adjustability needed for coordination
✅ Higher breaking capacity required (>25 kA)
✅ Some metering desired (with electronic trip)
✅ Moderate budget available
✅ Commercial/industrial application
✅ Field serviceability valued

Beispiel: Solar array mains, battery banks, motor feeders, sub-distribution

Choose ACB When:
✅ Current ≥ 800A (required) or 630-800A (beneficial)
✅ Full protection programmability essential
✅ Comprehensive metering mandatory
✅ Communication integration required
✅ Utility interconnection application
✅ Long-term asset (30-40 year lifespan)
✅ Budget adequate for advanced technology

Beispiel: Utility interconnection, main switchgear, data center mains, large ESS

Hybrid Approach for Large Systems

Optimal Strategy for multi-tier distribution:

Tier 1 (Upstream): ACB
– Main utility interconnection: 3200A ACB
– Full metering, communication, protection
– Cost: $30,000

Tier 2 (Distribution): MCCB
– Sub-distribution feeders: 400-800A MCCB
– Electronic trip, basic metering
– Quantity: 4-8 breakers
– Cost: $1000-1500 each

Tier 3 (Final Circuits): MCB
– Individual loads and strings: 16-63A MCB
– Fixed protection, low cost
– Quantity: 50-200 breakers
– Cost: $30-80 each

System Benefits:
– Optimized protection coordination (ACB → MCCB → MCB)
– Cost-effective (expensive ACB only where needed)
– Comprehensive monitoring (ACB provides system-level data)
– Maintainability (replace MCB easily, service ACB components)

Total System Cost Example (1 MW solar):
– 1× 3200A ACB: $30,000
– 8× 400A MCCB: $10,000
– 100× 20A MCB: $5,000
Insgesamt: $45,000 for complete protection system

Circuit breaker selection decision matrix showing MCB MCCB and ACB comparison criteria including current range cost features and application recommendations for DC electrical systems

Standards and Certification Differences

Applicable Standards by Type

All Three Types:
– IEC 60947-2: Low-voltage switchgear and controlgear – Circuit breakers
– UL 489: Molded-Case Circuit Breakers, Molded-Case Switches, and Circuit-Breaker Enclosures
– CSA C22.2 No. 5-18: Circuit Breakers

ACB-Specific:
– IEC 60947-1: General rules (applies to all, but ACB must meet enhanced requirements)
– UL 1066: Low-Voltage AC and DC Power Circuit Breakers Used in Enclosures
– IEEE C37.50: Low-Voltage AC Power Circuit Breakers Used in Enclosures

Testing Rigor:

MCB Testing:
– Sample testing: 6-12 units per rating
– Type tests: Breaking capacity, endurance, temperature rise
– Production testing: Continuity, dielectric strength, trip test (1 in 100)
Kosten: $50,000-100,000 per product line

MCCB Testing:
– Sample testing: 12-24 units per rating
– Additional tests: Short-circuit making capacity, coordination studies
– Production testing: More rigorous than MCB
Kosten: $100,000-300,000 per product line

ACB Testing:
– Sample testing: 24-48 units per rating
– Extensive tests: Mechanical endurance (10,000 operations), electromagnetic compatibility
– Production testing: Every unit tested at full rating
– Seismic qualification testing (utility applications)
Kosten: $500,000-2,000,000 per product line

Certification Cost Impact on Unit Price:
– MCB: Certification ≈ 5-10% of selling price
– MCCB: Certification ≈ 10-15% of selling price
– ACB: Certification ≈ 15-25% of selling price

Higher certification costs for complex equipment justify premium pricing.

Frequently Asked Questions (Comparison Focus)

Can I use an MCB instead of MCCB to save money?

Only if current rating <63A and no adjustability needed. In 50-125A overlap zone, MCB is acceptable for fixed-protection applications (cost savings 60-70%). However, MCCB offers higher breaking capacity, future adjustability, and longer lifespan. For critical circuits or coordination requirements, MCCB worth premium. Never use MCB beyond 125A rating—physically not available and would violate codes. Calculate 10-year TCO including maintenance and replacement—sometimes MCCB comparable despite higher initial cost.

What justifies the massive cost difference between MCCB and ACB?

ACB premium (20-100× MCCB cost) reflects: (1) Sophisticated electronics—color touchscreen, multiple microprocessors, communication interfaces worth $2000-5000 alone; (2) Comprehensive metering replacing $500-1500 external meter; (3) Enhanced mechanical construction—drawout mechanisms, heavy-duty contacts, extensive bus work; (4) Field serviceability—component replacement extends life to 30-40 years vs 20-30 for MCCB; (5) Rigorous testing and certification. For large installations (>800A), ACB feature set often comparable in value to MCCB + separate meter + communication gateway.

Do electronic MCBs exist, or only MCCBs have electronic trips?

True electronic trip units are MCCB/ACB exclusive. Some manufacturers market “electronic MCBs” but these typically have basic current sensing with LED indicators, not programmable protection. Confusion arises because: (1) Physical size similar to MCCB, (2) DIN rail mounting like MCB, (3) Current ratings in overlap zone (63-125A). Check specifications—if trip curves are adjustable and device has digital display, it’s an MCCB (or compact MCCB), not true MCB. True MCBs always have fixed thermal-magnetic protection, no user adjustment beyond physical trip curve selection.

How do I coordinate MCB, MCCB, and ACB in same system?

Use zone-selective coordination: larger upstream breakers have higher magnetic trip settings and longer time delays. Example 3-tier system: (1) MCB 20A C-curve: magnetic trip 100-200A, instantaneous; (2) MCCB 250A: magnetic trip 2500A, 0.2s delay; (3) ACB 2000A: short-time trip 8000A, 0.4s delay. For fault at MCB level (150A), only MCB trips. For fault at MCCB level (3000A), MCCB trips before ACB. Some ACBs support zone-selective interlocking via communication—ACB monitors downstream breaker status and extends delay if downstream can clear fault.

Can ACBs be used for low currents, or only high current applications?

ACBs available down to 630-800A, but economically impractical for lower currents. 800A ACB costs $8,000-15,000 while 800A MCCB costs $1,500-3,000 (5× difference). Below 630A, MCCB universally preferred. Exception: When integrated metering justifies cost—if project needs $2000 power meter anyway, ACB with metering at +$3000 premium nets to $1000 incremental cost for superior protection. Analyze total system cost including metering and communication equipment before dismissing ACB for “only” 800A application.

What happens if I mix breaker types with different breaking capacities?

Breaking capacity must be individually adequate at each installation point—upstream breaker doesn’t protect downstream breaker. Example: Fault current at Point A = 15kA, Point B (downstream) = 8kA. Installing 10kA MCB at Point A and 6kA MCB at Point B creates hazard—Point A breaker inadequate (15kA > 10kA). Correct: 15kA+ breaker at A, 10kA+ at B (even though 8kA available, use 10kA for margin). Mixing types (ACB upstream, MCCB mid-tier, MCB final) is fine as long as each breaker’s breaking capacity exceeds local fault current.

Are there environmental or sustainability differences between technologies?

MCBs use less material (0.1-0.5 kg plastic) but non-repairable (entire unit becomes waste). MCCBs use more material (0.5-5 kg) but some components replaceable. ACBs use most material (10-150 kg, mostly steel/aluminum) but fully serviceable with 30-40 year life. Lifecycle analysis: ACB has highest environmental impact per unit but lowest per kWh protected over lifespan. For green building certifications (LEED, BREEAM), ACB serviceability and longevity score well. SF₆-free arc extinction important—modern ACBs use air or vacuum, not SF₆. For sustainability-focused projects, prefer ACB for main breakers (longevity), MCB for branch circuits (material efficiency).

Schlussfolgerung

Selecting the optimal circuit breaker for DC applications requires balancing current requirements, feature needs, and budget constraints across MCB, MCCB, and ACB technologies. Each serves distinct roles in modern DC power systems—MCB for distributed protection at lowest cost, MCCB for adjustable mid-range protection with moderate investment, and ACB for comprehensive monitoring and control of high-current applications despite substantial capital expense.

Technology Selection Summary:

MCB Excellence: Dominates <63A applications where fixed protection suffices. Unmatched cost-effectiveness ($30-80 vs $300-500 MCCB), installation speed (minutes vs hours), and panel density (18-72mm width) make MCB ideal for solar string protection, small loads, and distribution circuits. Accept limitations: no adjustability, no metering, replace-not-repair lifecycle. MCCB Middle Ground: Optimal 125-2500A range with adjustability justifying cost premium. Electronic trip units ($500-2500) provide coordination capabilities and basic metering approaching ACB functionality at fraction of cost. Field serviceability and 20-30 year lifespan support industrial and commercial applications. Mandatory for battery systems >125A and solar array mains 200-630A.

ACB Premium Value: Required >1000A, valuable 630-1000A with metering needs. Comprehensive protection, integrated metering ($500-1500 value), communication interfaces, and 30-40 year serviceable life justify $15,000-50,000+ investment for utility interconnection, main switchgear, and grid-interactive systems. Feature richness transforms breaker from protection device to system monitoring hub.

Optimal System Design: Deploy technologies in coordination hierarchy—ACB at utility interface (monitoring and control), MCCB for sub-distribution (adjustability and capacity), MCB for final circuits (cost and density). This hybrid approach optimizes capital allocation while ensuring comprehensive, coordinated protection across all system levels.

For procurement decision-makers and system designers, technology selection transcends simple current rating lookup. Evaluate total cost of ownership, feature requirements beyond basic protection, communication infrastructure needs, and lifecycle management strategy to specify the circuit breaker technology delivering optimal value for each application tier.

Related Comparison Resources:
DC Circuit Breaker Technology Overview – Complete breaker specifications
DC Protection System Design – Multi-tier coordination strategies
DC Switch Disconnector Comparison – Load-break vs non-load-break devices

Specification Support: SYNODE provides technology selection consultation and lifecycle cost analysis for DC protection system procurement. Contact our sales engineering team for application-specific recommendations, vendor comparisons, and total cost of ownership modeling for projects >$50,000.

Zuletzt aktualisiert: Oktober 2025
Autor: SYNODE Product Selection Team
Technische Überprüfung: Senior Application Engineers, Procurement Specialists
Normen: IEC 60947-2:2016, UL 489:2021, UL 1066:2020

Teile deine Liebe
krad
krad

krad ist Spezialist für technische Inhalte bei SYNODE und verfügt über fundierte Fachkenntnisse im Bereich der solaren Gleichstromschutzsysteme. Mit mehr als einem Jahrzehnt Erfahrung im Bereich der erneuerbaren Energien hat krad bei mehr als 300 kommerziellen Solarprojekten in Nordamerika, Europa und Asien technische Beratung geleistet. Seine Arbeit konzentriert sich auf die Auslegung von Stromkreisen, die Implementierung von Überspannungsschutz und die Einhaltung elektrischer Vorschriften für Photovoltaikanlagen. krad ist für die Auslegung von PV-Solaranlagen zertifiziert und arbeitet regelmäßig mit Elektroingenieuren zusammen, um sicherzustellen, dass alle veröffentlichten Inhalte den IEC-, UL- und NEC-Normen entsprechen.

Artikel: 44