Dirección
304 North Cardinal
Dorchester Center, MA 02124
Horas de trabajo
De lunes a viernes: de 7.00 a 19.00 horas
Fin de semana: 10.00 A 17.00 HORAS
Dirección
304 North Cardinal
Dorchester Center, MA 02124
Horas de trabajo
De lunes a viernes: de 7.00 a 19.00 horas
Fin de semana: 10.00 A 17.00 HORAS

Understanding proper DC SPD wiring diagram procedures ensures effective surge protection while maintaining code compliance and system safety. This comprehensive installation guide provides detailed wiring diagrams, grounding methods, and step-by-step procedures for installing surge protection devices in solar photovoltaic systems. Whether you’re wiring SPDs at string level, combiner boxes, or inverter inputs, following these proven methods guarantees reliable protection performance.
Improper SPD wiring represents one of the most common installation defects found during electrical inspections. Short ground leads, incorrect conductor sizing, and poor termination practices dramatically reduce SPD effectiveness or create code violations. This guide eliminates wiring guesswork by providing clear diagrams and procedures verified for NEC compliance.
Before beginning SPD installation, thoroughly review system electrical drawings identifying DC conductor routing, voltage levels, and existing grounding infrastructure. Verify that specified SPD models match actual system DC voltage—600V, 1000V, or 1500V nominal—and continuous current ratings exceed string short-circuit current by required safety margins. Confirm combiner box or inverter enclosure sizes accommodate selected SPDs without overcrowding.
Identify existing equipment grounding conductor (EGC) paths and bonding connections that SPD grounding will integrate with. Locate the nearest grounding electrode connection point where SPD ground leads will terminate. Measure distances from planned SPD locations to grounding points to determine required conductor lengths avoiding excessive ground lead length that degrades SPD performance.
Review local authority having jurisdiction (AHJ) requirements for SPD installation beyond NEC minimums. Some jurisdictions mandate specific SPD placement locations, require additional protective devices, or specify particular wiring methods. Obtaining AHJ clarification before installation prevents costly rework when inspectors identify jurisdiction-specific requirements.
Installation Tools:
– Wire strippers rated for conductor sizes being terminated
– Torque screwdriver or wrench calibrated to SPD terminal specifications
– Multimeter capable of measuring DC voltage to 1500V minimum
– Label printer for permanent conductor and SPD identification
– Fish tape for pulling conductors through conduit runs
– Crimping tool for compression connectors (if used)
Materials and Hardware:
– SPD units verified for correct voltage rating and surge current capacity
– Conductors sized per Table 690.35 for SPD connections
– Equipment grounding conductors meeting Article 250 requirements
– Disconnect means if not integral to SPD (required per 690.35)
– Warning labels per 690.31(E) and SPD manufacturer instructions
– Cable management hardware (tie wraps, conduit clips, terminal blocks)
Información clave: Pre-assembling all tools and materials before starting prevents installation delays and maintains proper work sequence. Missing critical items mid-installation forces leaving partially complete work that creates safety hazards and code violations.
DC SPDs connect in parallel with protected equipment between DC circuit conductors and ground. This parallel connection allows SPDs to remain dormant during normal operation while activating during surge events to divert transient energy safely to ground. Proper parallel connection requires SPDs to connect as close as possible to protected equipment inputs minimizing conductor length that surge energy must traverse to reach the SPD.
String-level SPDs typically mount inside combiner boxes where individual string conductors terminate on common busbars. This location provides ideal access to positive and negative conductors for each protected string. SPDs install between string conductors and combiner box grounding busbar with minimal lead length maximizing protection effectiveness.
Combiner-to-inverter SPDs install at either combiner outputs or inverter DC inputs depending on system configuration and threat assessment. Installations at combiner outputs protect all downstream wiring and equipment from surges appearing at array. Inverter input installations provide final protection stage for sensitive power electronics but leave combiner-to-inverter wiring potentially exposed to induced transients.
| SPD Location | Connection Points | Typical Configuration | Ground Lead Length |
|---|---|---|---|
| String Level | String (+) to String (−) to EGC | Individual per string | ≤300mm (12″) |
| Salida del combinador | Combined (+) to Combined (−) to EGC | Single for all strings | ≤300mm (12″) |
| Entrada del inversor | DC (+) input to DC (−) input to chassis | One per inverter | ≤300mm (12″) |
NEC 690.35(A) requires SPD conductors to be not smaller than 14 AWG copper or 12 AWG aluminum. This minimum sizing ensures adequate mechanical strength and current-carrying capacity for surge diversion without creating additional impedance limiting SPD effectiveness. Many installations use 10 AWG conductors providing extra margin and better performance than code minimums.
SPD conductor length critically affects protection performance—longer conductors create higher inductance limiting how quickly surge energy reaches the SPD for diversion to ground. IEC standards recommend maximum combined lead length (line connection + ground connection) not exceeding 500mm (20 inches) with 300mm (12 inches) considered optimal. Shorter connections always provide better performance.
Ground conductor sizing follows NEC Article 250 requirements based on largest overcurrent device protecting the circuit. For PV systems, this typically references string fuse or circuit breaker ratings. Equipment grounding conductor (EGC) size should match or exceed the phase conductors for optimal surge current handling although code allows smaller sizing per Table 250.122.
⚠️ Importante: Never use stranded conductors smaller than 10 AWG for SPD connections—fine-strand conductors experience “skin effect” at surge frequencies (up to 1MHz) forcing current to conductor surfaces and dramatically increasing effective resistance. Solid conductors or coarse-strand flexible conductors perform better at surge frequencies.

Before beginning any SPD wiring work, verify complete system de-energization using proper lockout/tagout (LOTO) procedures. Open all DC disconnects between PV arrays and inverters removing all possible energy sources. Even with disconnects open, arrays generate voltage whenever light strikes modules creating shock hazards.
Use calibrated multimeter to verify zero voltage between all conductor pairs where SPD installation will occur. Test positive-to-negative, positive-to-ground, and negative-to-ground to confirm complete de-energization. Arrays may still generate voltage but it should not appear at installation location with upstream disconnects properly opened.
Cover array modules with opaque tarps or install during nighttime hours if absolute zero-voltage conditions are required. Check with SPD manufacturer instructions whether installation with energized conductors is permitted—most manufacturers require de-energized installation but some SPD designs allow live installation by qualified personnel.
Position SPD mounting location inside enclosure minimizing distances to connection points on busbars or terminal blocks. Most SPDs mount on standard 35mm DIN rail allowing easy positioning and removal. Ensure mounting location allows terminal access for conductor connections and status indicator visibility without requiring enclosure cover removal.
Verify adequate clearance around SPD for heat dissipation—most manufacturers specify minimum spacing to adjacent equipment. SPDs generate heat during normal operation and significantly more during surge events requiring airflow for cooling. Inadequate clearance causes premature SPD failure or performance degradation.
Secure SPD firmly to mounting rail or mounting surface using provided hardware. Loose mounting allows vibration damage and poor electrical connections. Verify mounting security by attempting to move SPD—properly mounted devices should not shift under moderate hand pressure.
NEC 690.35(C) requires disconnecting means for SPDs rated greater than surge protective device maximum continuous operating voltage (MCOV). This disconnect allows safe SPD replacement without de-energizing entire system. Some SPD models include integral disconnects (often DIN-rail mounted fuse holders) eliminating separate disconnect requirements.
When separate disconnect is required, install disconnect immediately adjacent to SPD minimizing unprotected conductor length between disconnect and SPD. Use disconnect rated for DC voltage and continuous current per system requirements. Label disconnect clearly identifying its function and relationship to SPD.
Fused disconnects provide both disconnect function and overcurrent protection for SPD and associated conductors. Select fuse ratings per SPD manufacturer recommendations—typically 10A to 32A depending on SPD model and expected surge exposure. Never use circuit breakers as SPD disconnects unless specifically approved by manufacturer for this application.
Begin conductor connections at SPD line terminals (positive and negative). Strip conductor insulation to length specified by terminal manufacturer—typically 10-12mm for screw terminals, 8-10mm for spring-loaded terminals. Avoid excessive exposed conductor that creates shock hazards or inadvertent contact with grounded surfaces.
Insert stripped conductor fully into terminal ensuring no bare conductor remains exposed outside terminal body. Tighten screw terminals to torque specified by SPD manufacturer—typically 0.9 to 1.4 N⋅m (8 to 12 lb-in) for M4 terminals, higher for larger terminals. Use calibrated torque driver preventing both under-tightening (poor contact) and over-tightening (conductor damage).
For spring-loaded terminals, insert conductor until it reaches terminal stop then verify connection by pulling conductor with moderate force. Properly seated connections resist pull-out forces exceeding 50N (11 lbf). If conductor pulls free, inspect terminal and conductor for damage, correct any issues, and reinstall.
Consejo profesional: Take photos of all conductor connections before closing enclosures—these reference photos prove invaluable during troubleshooting and inspections. Photos also document proper installation procedures for future reference by other technicians unfamiliar with the installation.
Equipment grounding conductor (EGC) connection to SPD ground terminal represents the most critical connection affecting surge protection performance. Route EGC from SPD ground terminal to enclosure grounding busbar or grounding electrode connection using shortest possible path. Avoid loops, coils, or unnecessary bends that increase conductor inductance degrading SPD effectiveness.
Strip EGC insulation to terminal requirements and insert fully into SPD ground terminal. Tighten to specified torque ensuring excellent electrical contact. Poor ground connections cause voltage rise at SPD terminals during surge events potentially allowing damage to protected equipment despite SPD presence.
If SPD ground terminal and enclosure ground bus are not within direct-line distance, use large-radius bends (minimum 150mm/6″ radius) rather than sharp 90-degree bends. Surge current flowing through sharp bends creates localized magnetic fields that induce voltages opposing current flow, effectively increasing conductor impedance.
Complete SPD wiring by terminating line conductors at system busbars or terminal blocks. Positive conductor routes to positive busbar, negative to negative busbar, maintaining proper polarity. Use separate terminals or terminal positions for SPD conductors rather than doubling conductors in terminals already containing circuit conductors.
Follow same stripping, insertion, and torque procedures used for SPD terminal connections. Verify terminal ratings exceed expected current including both continuous current and surge current contributions. Some jurisdictions require dedicated terminals for SPD connections to facilitate future SPD replacement without disturbing other circuit connections.
Label all SPD conductors at both ends with permanent identification indicating “SPD Connection” and referencing specific SPD unit if multiple SPDs exist in enclosure. Labeling facilitates future maintenance and prevents accidental disconnection during unrelated work.

SPD effectiveness depends critically on proper grounding connecting surge current to earth with minimum impedance. Understanding the distinction between equipment grounding conductor (EGC) and grounding electrode conductor (GEC) ensures proper SPD ground connections meeting both code requirements and optimal performance criteria.
Equipment grounding conductor (EGC) per NEC Article 250 provides ground-fault current return path from equipment to system grounded conductor or neutral. For SPD applications, EGC connects SPD ground terminal to enclosure grounding busbar creating electrical bond between SPD and equipment chassis. EGC sizing follows NEC Table 250.122 based on circuit overcurrent protection rating.
Grounding electrode conductor (GEC) connects grounding busbar to grounding electrode system (ground rods, concrete-encased electrodes, building steel, etc.) providing true earth ground connection. GEC represents final path for surge current diverted by SPDs to dissipate into earth. GEC sizing follows NEC Table 250.66 based on service conductor size—typically larger than EGC.
The critical concept: SPDs must connect to both EGC (for bonding to equipment) and ultimately through GEC to earth ground (for surge current dissipation). Many installations incorrectly bond SPDs only to equipment chassis without verified connection to grounding electrode system reducing SPD effectiveness significantly.
Ground lead inductance represents the primary factor limiting SPD surge diversion performance. Every conductor exhibits inductance (typically 300-500nH per meter for typical building wire) that opposes rapid current changes. During fast-rising surge events (sub-microsecond rise times), even short ground leads develop significant voltage drop across lead inductance potentially exceeding protected equipment voltage ratings.
Calculate approximate voltage drop across ground lead inductance using V = L(di/dt) where L is lead inductance and di/dt is surge current rate of change. For 1-meter ground lead (400nH) conducting 10kA surge with 1μs rise time: V = 400nH × (10,000A/1μs) = 4,000V. This 4kV voltage adds to SPD clamping voltage, potentially allowing equipment damage despite SPD presence.
Minimize ground lead inductance through multiple proven techniques:
Shortest possible length: Each centimeter saved reduces inductance proportionally. Route ground conductors directly to grounding busbar without unnecessary routing detours.
Largest practical conductor size: Larger conductors exhibit lower inductance per unit length. Using 6 AWG instead of 14 AWG reduces inductance approximately 30%.
Avoid loops and coils: Any conductor loop creates magnetic field increasing inductance dramatically. Keep ground conductors straight with large-radius bends only when necessary.
Parallel ground paths: Multiple ground conductors in parallel reduce combined inductance. Where feasible, use two ground conductors instead of one for critical SPD connections.
| Ground Lead Length | Approximate Inductance | Voltage Drop @ 10kA/μs | Performance Rating |
|---|---|---|---|
| 150mm (6″) | 60nH | 600V | Excelente |
| 300mm (12″) | 120nH | 1,200V | Bien |
| 500mm (20″) | 200nH | 2,000V | Acceptable |
| 1000mm (40″) | 400nH | 4,000V | Poor—Rework Required |
⚠️ Importante: Many electrical inspectors measure ground lead length during inspections. Leads exceeding 300mm (12 inches) often trigger correction notices requiring rework. Plan SPD mounting locations allowing code-compliant ground lead lengths before beginning installation.
Systems with multiple SPD installations require careful attention to ground bonding preventing circulating ground currents and ensuring all SPDs share common ground reference. Each SPD should connect to local equipment ground busbar which then bonds to building grounding electrode system through single GEC connection per building area.
Avoid creating multiple parallel ground paths between different system sections that create ground loops allowing stray currents to circulate during normal operation. Ground loops also create differential voltages between supposedly equipotential ground points potentially causing nuisance SPD activation or inadequate surge diversion.
In large PV installations spanning multiple roof areas or buildings, establish single-point ground connection at main service entrance or designated grounding junction. All equipment ground busbars in combiner boxes, inverters, and other enclosures bond together and ultimately to this single grounding point preventing multiple earth connections that create ground loops.
NEC Article 690.35 specifies mandatory surge protective device requirements for photovoltaic systems located where lightning exposure exists. While 690.35 doesn’t mandate SPDs for all installations, best practice recommends SPD protection regardless of code requirements given high lightning vulnerability of elevated PV arrays and costly equipment damage potential.
Section 690.35(A) requires “a listed surge protective device” noting use of word “a” rather than plural “devices.” However, effective protection typically requires multiple SPDs at different system locations creating defense-in-depth protection. Single SPD installations rarely provide adequate protection except in smallest residential systems with minimal conductor runs.
SPDs must be “listed” per 690.35(A) requiring third-party certification by nationally recognized testing laboratory (NRTL) such as UL, ETL, or CSA. Listed devices carry certification mark on nameplate or documentation proving compliance with applicable standards. Using non-listed SPDs violates code and insurance requirements.
Section 690.35(B) specifies SPD connection locations: “at the DC source or DC output circuits.” This language allows flexibility installing SPDs at array location (DC source), inverter inputs (DC output circuits), or both locations for enhanced protection. Installation at both locations provides optimal protection but at higher cost.
The section further requires SPDs be “connected to the circuit conductors from the ungrounded conductors to ground.” This phrasing mandates SPDs connect between ungrounded (positive and negative) DC conductors and equipment ground, not between positive and negative conductors only. Proper connection requires three terminal SPDs or two separate SPDs covering positive-to-ground and negative-to-ground paths.
Section 690.35(C) requires disconnect means for SPDs unless integral to SPD assembly. Disconnecting means must be readily accessible allowing SPD replacement without de-energizing entire PV system. This requirement recognizes SPDs as maintenance items subject to periodic replacement after surge exposure or aging. Installations violating this requirement force complete system shutdown for routine SPD replacement.
Although 690.35 doesn’t specify minimum conductor size, general wiring rules in NEC Article 310 and 250 establish sizing requirements. Most designers specify 10 AWG minimum for SPD connections providing adequate current capacity and mechanical strength while meeting inspector expectations.
Section 690.35(D) addresses overcurrent protection for SPD conductors requiring overcurrent protection per Article 240 unless conductors meet tap rules or other exceptions. Many designers install fuses or circuit breakers protecting SPD branch circuits from overcurrent conditions. Fuse ratings typically 10A to 32A depending on SPD continuous current rating and expected surge exposure.
Some SPD models include integral overcurrent protection eliminating separate protection device requirements. Integrated protection simplifies installation and reduces parts count but requires complete SPD replacement if overcurrent device operates rather than simple fuse replacement.

Problema: Installing SPDs with ground leads exceeding 300mm (12 inches) dramatically reduces surge protection effectiveness. Long ground conductors exhibit high inductance creating voltage drop during surge events that adds to SPD clamping voltage potentially allowing equipment damage. This represents the single most common SPD installation defect found during electrical inspections.
Escenarios comunes:
– Mounting SPDs far from enclosure grounding busbar requiring extended ground conductor routing
– Routing ground conductors through wire channels or cable trays adding unnecessary length
– Using bundled multi-conductor cables for SPD connections where ground conductor has excess slack
Corrección: Relocate SPD mounting position minimizing distance to grounding busbar or reroute ground conductor using most direct path possible. Many installations require enclosure modifications (drilling mounting holes, relocating DIN rail) to achieve proper ground lead length. Consider adding auxiliary ground busbar near SPD if existing ground busbar location prevents code-compliant installation.
Problema: Loose conductor connections at SPD terminals or busbars create high-resistance contact points that heat excessively during surge events and continuous operation. Inadequate torque commonly occurs when installers use non-calibrated tools or guess at proper tightness level. Loose connections fail electrical inspection and pose fire hazard during operation.
Escenarios comunes:
– Using adjustable wrenches or pliers instead of calibrated torque drivers
– Overtightening one terminal and under-tightening others due to inconsistent force application
– Failing to verify terminal torque after initial installation during final quality inspection
Corrección: Always use properly calibrated torque screwdriver or wrench set to SPD manufacturer specified torque value. Typical terminal torque specifications range 0.9 to 1.4 N⋅m (8 to 12 lb-in) for standard M4 terminals. Document achieved torque values on installation checklist and verify all connections before closing enclosure.
⚠️ Importante: Some SPD models use spring-loaded terminals requiring insertion force only without torque adjustment. Verify installation method with manufacturer instructions—attempting to torque spring-loaded terminals damages terminal mechanism and creates poor connections.
Problema: NEC 690.35(C) mandates accessible disconnect means for SPDs allowing safe replacement. Installations omitting disconnects or using inaccessible disconnect locations violate code and create safety hazards during SPD replacement requiring technicians to work on energized conductors. Missing disconnects fail electrical inspection requiring costly rework.
Escenarios comunes:
– Assuming integral SPD terminal covers satisfy disconnect requirement (they don’t)
– Installing disconnect inside inverter enclosure accessible only by inverter service technicians
– Using circuit breakers as disconnects without verifying manufacturer approval for this application
Corrección: Install readily accessible fused disconnect immediately adjacent to SPD when not integral to SPD assembly. Use disconnect rated for system DC voltage with fuse rating per SPD manufacturer recommendation. Label disconnect clearly with “SPD Disconnect—Do Not Remove Under Load” warning.
Problema: Connecting SPD positive terminal to negative busbar and negative terminal to positive busbar creates incorrect protection or potential damage to SPDs using polarity-sensitive protection elements. While many SPD designs tolerate reverse polarity without immediate failure, protection performance degrades significantly. Some SPD types (particularly those using semiconductor elements) fail immediately when reverse connected.
Escenarios comunes:
– Misreading conductor labels in crowded enclosures with multiple wire colors
– Assuming both SPD line terminals are identical without checking polarity markings
– Using unmarked busbars in combiner boxes without verifying which is positive vs negative
Corrección: Verify conductor polarity at both SPD end and busbar end before making final connections. Use multimeter to confirm positive conductors show expected voltage relative to negative when system is energized. Follow consistent color coding (red positive, black negative) throughout installation. Label all SPD terminals and busbars clearly with polarity markings visible during maintenance.
Before energizing newly installed SPD circuits, perform comprehensive inspection verifying all installation requirements. Visual inspection catches most common errors preventing equipment damage or code violations during initial energization. Systematic checklist prevents overlooking critical details during rush to commission system.
Verify correct SPD model installed matching system DC voltage rating and surge current specifications. Confirm SPD voltage rating equals or exceeds system maximum DC operating voltage with appropriate safety margin. Check SPD surge current rating (Iimp for Type 1, In for Type 2) meets system requirements per threat assessment and manufacturer recommendations.
Inspect all conductor connections at SPD terminals and system busbars verifying proper insertion depth, torque application, and lack of exposed conductors outside terminals. Ensure conductors show no signs of insulation damage, nicks, or compression marks indicating improper handling. Verify wire markings or labels identify conductor function and destination.
Measure ground lead length from SPD ground terminal to grounding busbar confirming ≤300mm (12 inches) maximum length. Verify ground conductor routing follows most direct path without unnecessary loops, coils, or sharp bends. Check ground conductor size meets minimum 10 AWG requirement (larger is better).
Using multimeter set to resistance (Ω) mode with test leads at SPD disconnected, measure resistance between each SPD line terminal and ground terminal. Readings should show high resistance (megohms) indicating SPD in standby (non-conducting) state. Low resistance readings (less than 1kΩ) suggest SPD damage requiring replacement before energization.
Measure resistance between SPD line terminals and grounding busbar verifying ground conductor provides low-resistance path to ground. Typical readings should show less than 0.5Ω for properly installed 10 AWG ground conductors under 300mm length. Higher resistance indicates poor connections requiring correction.
Test continuity of equipment grounding conductor path from SPD ground terminal through enclosure grounding busbar to grounding electrode conductor. This end-to-end continuity test verifies complete ground path without opens or high-resistance connections. Readings exceeding 1Ω suggest grounding system problems requiring investigation and correction.
With visual inspection and electrical testing complete, energize system following manufacturer procedures. Most SPDs provide visual status indicators (typically green LED or mechanical flag) confirming proper operation. Verify status indicator shows “healthy” or “operational” state immediately after energization.
Measure voltage across SPD terminals using multimeter set to DC voltage mode rated for system voltage. Voltage reading should equal system operating voltage confirming SPD in parallel connection seeing full circuit voltage. Voltage significantly lower than expected suggests series connection error or parallel conductor fault.
Monitor SPD status indicators during first 24 hours operation noting any changes suggesting SPD activation or failure. Many SPDs include alarm contacts allowing remote monitoring of SPD status through building management systems. Connect alarm contacts to monitoring system per manufacturer wiring diagrams enabling automated alerts for SPD failures.
Establish regular SPD inspection schedule checking status indicators and physical condition quarterly minimum. Visual inspection catches SPD failures before they compromise system protection allowing timely replacement. Schedule inspections during other routine maintenance visits to minimize site access costs.
Inspect SPD status indicators verifying green “healthy” status on all devices. Failed status indicators (red, yellow, or dark) require immediate SPD replacement. Document status of all SPDs in maintenance log with inspection date and inspector name creating historical record of SPD condition.
Examine SPD housing and terminals for signs of overheating (discoloration, melting, burning smell) indicating excessive current flow or poor connections. Check conductor insulation near terminals for heat damage or brittleness suggesting thermal stress. Any signs of overheating require immediate investigation and correction.
Replace SPDs immediately when status indicators show failure condition regardless of time since installation. Failed SPDs no longer provide surge protection leaving equipment vulnerable to damage. Many SPD failures occur after major surge events—inspect all SPDs after thunderstorms passing within 5km of installation.
Replace SPDs reaching manufacturer specified service life even when status indicators show healthy condition. Typical SPD service life ranges 3 to 10 years depending on surge exposure and environmental conditions. Document installation dates allowing proactive replacement before end-of-life failures.
Consider replacing SPDs when status indicators frequently show activation (temporary yellow or flashing indicators) suggesting SPD approaching capacity limits. Frequent activations indicate high local lightning activity exceeding original threat assessment. Upgrading to higher-capacity SPD types (Type 1 instead of Type 2, higher surge current ratings) provides better protection in these situations.
After SPD replacement, repeat commissioning procedures verifying proper installation of replacement device. Check status indicators, measure voltages, and verify alarm contact operation. Document replacement date, new SPD model and serial number, and any changes to system protection configuration.
Investigate cause of failed SPD to identify potential system issues. SPDs failing shortly after installation suggest wiring errors, inadequate grounding, or undervoltage SPD selection. Multiple SPDs failing simultaneously indicate severe surge event or ground system fault. Address root causes preventing repetitive failures.
NEC 690.35 specifies minimum 14 AWG copper conductors for SPD connections but most professional installations use 10 AWG providing better surge current handling and lower inductance. The conductor size directly affects SPD performance—larger conductors (6 AWG or 4 AWG) further reduce inductance improving protection effectiveness particularly for high-threat installations.
Ground conductors should match or exceed line conductor size with 10 AWG considered practical minimum. Some designers specify ground conductors one size larger than line conductors recognizing critical importance of low-inductance ground path. Conductor length matters more than size—even large conductors lose effectiveness when excessively long.
Calculate conductor size considering both continuous current rating and surge current capacity. SPD line conductors see minimal continuous current (leakage current typically <1mA) but must withstand surge currents potentially exceeding 100kA briefly. While conductors survive these extreme currents due to brief duration, larger sizes provide better surge current distribution reducing localized heating.
Industry best practice recommends combined line and ground lead length not exceeding 500mm (20 inches) with ground lead alone under 300mm (12 inches). Shorter leads always provide better performance—installations achieving 150mm (6 inch) ground leads deliver optimal protection. The voltage drop across ground lead inductance adds directly to SPD clamping voltage potentially allowing equipment damage if leads are excessive length.
Each 100mm (4 inches) of lead length adds approximately 40nH inductance. During 10kA surge with 1μs rise time, this creates 400V voltage drop per 100mm of lead length. For 1000V-rated equipment with 1400V insulation level, keeping added voltage below 400V requires ground leads under 100mm—a challenging but achievable target with careful planning.
When physical constraints prevent achieving optimal ground lead length, use largest practical conductor size and avoid any loops or coils in conductor routing. Consider adding supplemental ground busbars closer to SPD locations or relocating SPDs to positions allowing shorter ground connections. Investing time optimizing ground lead length during installation provides protection benefits lasting system lifetime.
Most SPD manufacturers prohibit installation on energized systems requiring complete de-energization before beginning work. Solar PV systems present unique challenges because arrays generate voltage whenever illuminated making true de-energization difficult. For safest installation, cover arrays with opaque tarps or schedule installation during nighttime hours achieving zero-voltage conditions.
Some specialized SPD designs allow “hot work” installation by qualified electricians using appropriate personal protective equipment (PPE). These installations require arc-rated clothing, insulated tools, and detailed safe work procedures. Never attempt energized SPD installation without manufacturer explicit approval, proper training, and full arc-flash PPE rated for system fault current and voltage.
When arrays must remain uncovered during installation, open all upstream DC disconnects isolating work area from array voltage. Verify zero voltage at work location using appropriately rated multimeter before beginning conductor connections. Even with isolation, maintain arc-flash awareness throughout installation—array voltage can appear at work location through unexpected ground faults or isolation device failures.
SPD behavior under reversed polarity depends on internal protection element types used. MOV-based SPDs (most common type) are non-polarized devices tolerating reverse connection without immediate damage—MOVs conduct bidirectionally regardless of polarity. However, even MOV-based SPDs may include other components (indicating circuits, alarm contacts) that are polarity-sensitive and malfunction when reversed.
Semiconductor-based SPDs using silicon avalanche diodes are highly polarity-sensitive and fail immediately when reverse-connected. These devices conduct surge current in only one direction—reverse connection allows full surge voltage to appear at protected equipment without SPD activation. Some semiconductor SPD designs include reverse polarity protection but most do not making correct polarity critical.
Hybrid SPDs combining multiple protection technologies (GDT + MOV + diode) show mixed reverse polarity tolerance depending on architecture. Always verify correct polarity before energizing newly installed SPDs. Manufacturers mark polarity on SPD housing using + and − symbols, color coding, or terminal labels. Follow these markings exactly during installation preventing protection failures or SPD damage.
Optimal SPD placement strategy depends on installation size, array exposure, and threat assessment. Small residential systems (2-4 strings) typically use single SPD at combiner output protecting entire array with adequate effectiveness and minimal cost. Larger commercial systems (6+ strings) benefit from string-level SPDs providing independent protection for each string plus additional SPD at combiner output creating two-stage protection.
String-level SPDs provide superior protection by intercepting surges immediately at point of entry into electrical system before energy couples onto other strings. This independent string protection prevents single string lightning strike from damaging other strings or downstream equipment. The additional cost of multiple SPDs is justified in high-exposure installations or systems protecting expensive inverters.
Arrays spread across multiple roof sections or buildings definitely require SPDs at each location. Long DC conductor runs between separated arrays act as antennas collecting induced surge energy even without direct strikes. Local SPD protection at each array location intercepts this energy before it propagates through inter-building wiring potentially damaging equipment at distant locations.
SPD terminal torque specifications vary by manufacturer and terminal size but typical values range 0.9 to 1.4 N⋅m (8 to 12 lb-in) for standard M4 screw terminals used in most mid-size SPDs. Larger SPDs with M5 or M6 terminals may specify 1.5 to 2.5 N⋅m (13 to 22 lb-in). Always verify manufacturer specifications in installation instructions—generic values risk either under-tightening (poor contact) or over-tightening (conductor or terminal damage).
Use calibrated torque screwdriver or wrench set to specified value rather than guessing tightness by feel. Human perception of torque varies widely—studies show technicians using “feel” achieve actual torque ranging from 40% to 200% of target value. This inconsistency creates unreliable connections affecting both safety and performance. Calibrated tools cost under $100 but eliminate this variability delivering consistent results.
Some SPD designs use spring-loaded push-in terminals eliminating torque requirements—simply insert stripped conductor until it clicks or reaches physical stop. These terminals automatically apply correct contact force. Verify proper insertion by pulling conductor with moderate force—properly seated conductors resist pull-out. Never attempt to torque spring-loaded terminals using tools as this damages terminal mechanism.
Most modern SPDs include visual status indicators (LED lights or mechanical flags) showing device condition. Green indicator typically signals healthy operation while red or dark indicator shows failure requiring immediate replacement. Inspect status indicators quarterly during routine maintenance noting any changes in status suggesting SPD approaching end of life.
Some SPD failures occur suddenly after major surge events while others degrade gradually over years. Sudden failures usually result from surge currents exceeding SPD rating destroying internal protection elements. Gradual failures stem from cumulative exposure to numerous smaller surges eventually exhausting SPD capacity. Both failure modes trigger status indicators when properly functioning.
Many commercial SPDs include remote alarm contacts allowing automated monitoring integration with building management systems. Connect these alarm contacts per manufacturer wiring diagrams enabling automated notifications when SPD failures occur. Remote monitoring proves especially valuable for remote sites where quarterly manual inspections are impractical allowing immediate failure notification and prompt replacement scheduling.
Proper DC SPD wiring represents critical factor determining protection effectiveness in solar photovoltaic systems. Following the detailed procedures, grounding methods, and wiring diagrams presented in this guide ensures installations meet NEC 690.35 requirements while delivering maximum surge protection performance. Short ground leads, correct conductor sizing, proper termination torque, and systematic testing create reliable protection lasting system lifetime.
Principales conclusiones:
1. Minimize ground lead length to ≤300mm using shortest direct path from SPD to grounding busbar
2. Use 10 AWG minimum conductors for SPD connections with larger sizes providing better performance
3. Apply manufacturer specified terminal torque using calibrated tools ensuring reliable connections
4. Verify SPD voltage rating matches or exceeds system maximum DC voltage with appropriate safety margin
5. Install accessible disconnect means per NEC 690.35(C) allowing safe SPD replacement without system shutdown
Investing proper time and attention during SPD installation delivers protection benefits throughout system operational life. Poor installations compromise protection effectiveness leaving expensive equipment vulnerable to surge damage. The procedures and diagrams in this guide eliminate installation uncertainties delivering code-compliant installations meeting manufacturer performance requirements.
Related Resources:
– DC SPD for Solar Systems: Type 1 vs Type 2 Protection
– DC Circuit Breaker Installation Procedures
– PV Combiner Box Wiring and Grounding Standards
Ready to specify compliant DC SPD installations for your projects? Contact our technical team for project-specific wiring diagrams, grounding system design assistance, and installation procedure verification. We help ensure proper SPD installation meeting NEC requirements and delivering maximum surge protection performance for solar PV systems.
Última actualización: December 2025
Autor: Equipo técnico de SYNODE
Revisado por: Departamento de Ingeniería Eléctrica