DC Surge Protective Device for PV (48V–1000V) | DC SPD In 20kA / Imax 40kA

  • ✔ Type 2 DC surge protector (PV system up to 1000 VDC)
  • ✔ Discharge capacity: In 20 kA, Imax 40 kA (8/20 µs)
  • ✔ Fast response <25 ns, low residual voltage
  • ✔ Pluggable cartridge, DIN-rail mount, thermal disconnector
  • ✔ Optional remote alarm contacts
  • ✔ Standard: IEC 61643-31
Get A Quotation
Category:

DC Surge Protective Device (DC SPD) — C40 Series (48V / 220V / 500V / 600V / 1000V)

The C40 series DC surge protective device (SPD) is engineered for photovoltaic DC buses and other DC networks. It uses parallel installation to provide reliable surge suppression without affecting normal system operation.

Key Features

  • Wide clearance & creepage distance; withstands high voltage; suitable for high-altitude areas.
  • Pluggable modular cartridge; standard 35mm DIN-rail mounting.
  • High-quality lightning-proof components for stable performance.
  • Hot-melt + over-current dual protection circuit.
  • Status window: green = normal, red = replacement required.
  • Low residual voltage, fast response <25ns, strong discharge capability.
  • Optional remote signaling contact for SCADA/BMS.

Main Technical Parameters — C40 Series

ModelMax Continuous Operating Voltage
Uc (DC)
Nominal Discharge Current
In (8/20 μs)
Max Discharge Current
Imax (8/20 μs)
Voltage Protection Level
Up
Response TimeOperating EnvironmentCross Section of L/NProtection ClassOutline Size (mm)
C40-4848V DC20 kA40 kA~ 350 V<25 ns−40 °C ~ +80 °C≥ 10 mm²IP2036 × 66 × 90
C40-220220V DC20 kA40 kA~ 1.8 kV<25 ns−40 °C ~ +80 °C≥ 10 mm²IP2036 × 66 × 90
C40-500500V DC20 kA40 kA~ 2.5 kV<25 ns−40 °C ~ +80 °C≥ 10 mm²IP2036 × 66 × 90
C40-600600V DC20 kA40 kA~ 2.8 kV<25 ns−40 °C ~ +80 °C≥ 10 mm²IP2036 × 66 × 90
C40-10001000V DC20 kA40 kA~ 3.5 kV<25 ns−40 °C ~ +80 °C≥ 10 mm²IP2054 × 66 × 90

Notes: Values follow the supplied datasheet. Update cells if your latest engineering data differs.

Drawings

Dimension

DC SPD C40 series dimension drawing


Wiring Diagram (Parallel)

DC SPD C40 series wiring diagram (parallel connection)


FAQ

Which systems is the C40 series designed for?
Photovoltaic DC buses and other DC networks from 48V to 1000V. Select the model by matching Uc.
How do I choose among C40-48 / 220 / 500 / 600 / 1000?
Choose by the max continuous voltage Uc of your DC bus, then verify surge ratings (In/Imax) and target a low Up.
Where should the SPD be installed?
Install at the DC combiner/distribution panel with parallel wiring, short leads, and a reliable PE bar. Follow the diagram.
Is the module replaceable and is remote signaling available?
Yes. The cartridge is pluggable for quick replacement; an optional alarm contact can be wired to SCADA/BMS.
What environmental and wiring requirements apply?
Operating temperature −40°C ~ +80°C, cross-section of L/N ≥10mm², enclosure IP20.
How should surge protection be coordinated?
Coordinate with upstream over-current protection (e.g., DC fuse/breaker) and inverter limits to ensure selectivity and safety.